SMOKE VENTILATION CONTROL PANELS

SMOKE VENTILATION CONTROL PANELS

SMOKE VENTILATION CONTROL PANELS A very versatile range of smoke ventilation control panels, provided of back-up batteries: they operate 24

SMOKE VENTILATION CONTROL PANELS

A very versatile range of smoke ventilation control panels, provided of back-up batteries: they operate 24 Vdc actuators for smoke
and heat extraction in case of fire, and control the automation of single or multiple windows for natural ventilation even in a
multy-storey building.
The opening command for smoke extraction is controlled by smoke detectors, emergency push buttons, fire alarm systems or Building
Management Systems (BMS) by “free potential – normally closed” inputs. The installation of the emergency push button (MCP –
manual control point) is compulsory because, in addition to allowing manual emergency control, it also provides display of fault /
emergency warnings, and can be used for easy, remote resetting.
In order to provide comfort and energy saving, the natural ventilation is granted by operating automatically the windows, according
to the environmental conditions detected by the sensors. Windows can be manually controlled through push buttons or key switches
in 2 different ventilation zones.
C-SV and C-SV IB control panels have been designed and tested according to the European Standard EN 12101-10 and prEN 12101-9.
They have been certified as Smoke and Heat Control Systems according to the European Standard EN 12101-10:2005 + AC:2007 by IFT
Rosenheim (not for C-SV 13A and C-SV IB 13A versions)

SMOKE VENTILATION CONTROL PANELS – ACCESSORIES

 

OPTICAL SMOKE DETECTOR – 36418Q

Smoke detection by infrared light diffusion for Tyndall effect. It is certified according to the UNI EN 54 – 7/9 regulations. Alarm signal through the red led.
RESPONSE TIME 3 sec approx.
VOLTAGE SUPPLY 24 V (min. 10 V, max. 30 V)
TEMPERATURE RANGE -10° + 80° C
DEGREE OF HUMIDITY < 95%
MAX AIR SPEED 10 m/s
DETECTED SURFACE 40 m2
A frequent cleaning, especially in dusty environments, is recommended.

EMERGENCY PUSH BUTTON – 42140N

It’s necessary to break the safety glass to operate the emergency button. Emergency push button allow to control by LEDs the status of the system, reset the control panels and close the window at the end of the emergency

 

FLUSH MOUNT DOUBLE PUSH BUTTON – 41019H

Once connected to control panel allows to operate all window for natural ventilation.

 

NV KEY SWITCH – 41789B

Once connected to control panel allows to operate all window for natural ventilation.
If properly connected to C-SV, it can be used to send an emergency closing command.

 

WS WIND SENSOR – 37185V

It emits a variable signal according to
the wind intensity and acts on the
control panel as the rain sensors do.

TH THERMOSTAT – 40675K

The thermostat opens or closes
windows when temperature settings
are exceeded. Built in on/off switch.

 

ACOUSTIC ALARM DEVICE – 40892C

Outward self-fed siren 24 V, stainless
steel box with polycarbonate cover,
sound power 115 dB,
voltage supply 24V – 2 A,
battery 12 V, 2 Ah.
Dimensions: 236x280x99 mm

 

RS RAIN SENSOR – 40450K

In case of rain, the rain sensor sends
the signal for window automatic closing.

 

CO2 – 41773L

The CO2 sensor, if present, has the
priority on the manual control. Suitable
for conference and meeting rooms,
offices, schools/nurseries, passive and
low-energy buildings.
2 switch outputs CO2 controlled for
2 stage control, with manual and
automatic mode as well as display of
switching status.
3x 0–10 V outputs for CO2,
temperature and relative humidity.
Compatible C-SV, IB-SV only

 

DIAGNOSTIC KIT (CABLE + SOFTWARE) – 41853M

In the event of anomalies or installation
problems, it is possible to interrogate
the C-SV control panels using a special
diagnostic USB cable connected to a
simple computer. A dedicated software
allows you to monitor in real time the
operating parameters of the control
panel (primary power supply, battery
voltage, etc.) and to trace the origin of
any faults by reading the associated
error code.

 

BATTERIES FOR C-SV AND C-SV IB

40911V
Spare part for C-SV and C-SV IB control panel 4A or 8A, formed by two pieces of 12 V, 4,5 Ah batteries.
41921C
Spare part for C-SV and C-SV IB control panel 13A or 20A, formed by two pieces of 12 V, 9 Ah batteries.

Label Value
ALIMENTAZIONE
Tensione di alimentazione 100-250 Vac, 50-60 Hz
Modalità pilotaggio motori Inversione di polarità
Uscita tensione ausiliaria 24 Vdc
Corrente nominale 4 A / 8 A / 13 A / 20 A
Batterie di back up 2x 12 Vdc (batterie al piombo)
CARATTERISTICHE
Numero zone emergenza 1
Numero zone ventilazione naturale 2
Sensori fumo/calore Max 10
Pulsanti di emergenza Max 10 (pulsantiera integrata sul fronte della centrale solo nella versione IB)
Comandi chiusura emergenza Max 10 (normalmente contatto aperto)
Uscita segnalazione emergenza Contatto pulito (es. allarme acustico)
Pulsanti ventilazione Esterni (pulsantiera integrata sul fronte della centrale solo nella versione IB)
Sensore pioggia Max 1
Sensore vento Max 1
Sensore CO2 Max 1
Termostato Max 1

MODELLI DISPONIBILI

MODELLO

CODICE

CORRENTE
NOMINALE

PULSANTIERA

BATTERIE

DIMENSIONI mm (“)

C-SV 4A

41736A

4A

Non inclusa

Incluse

300x300x150
(11.8x11.8x5.9)

C-SV 8A

41737B

8A

Non inclusa

Incluse

300x300x150
(11.8x11.8x5.9)

C-SV 13A

41918Z

13A

Non inclusa

Incluse

400x400x150
(15.7x15.7x5.9)

C-SV 20A

41874H

20A

Non inclusa

Incluse

400x400x150
(15.7x15.7x5.9)

C-SV IB 4A

41738C

4A

Integrata frontalmente
su centrale

Incluse

300x300x150
(11.8x11.8x5.9)

C-SV IB 8A

41739D

8A

Integrata frontalmente
su centrale

Incluse

300x300x150
(11.8x11.8x5.9)

C-SV IB 13A

41919A

13A

Integrata frontalmente
su centrale

Incluse

400x400x150
(15.7x15.7x5.9)

C-SV IB 20A

41875I

20A

Integrata frontalmente
su centrale

Incluse

400x400x150
(15.7x15.7x5.9)

No data found.