SMOKE VENTILATION CONTROL PANELS
A very versatile range of smoke ventilation control panels, provided of back-up batteries: they operate 24 Vdc actuators for smoke
and heat extraction in case of fire, and control the automation of single or multiple windows for natural ventilation even in a
multy-storey building.
The opening command for smoke extraction is controlled by smoke detectors, emergency push buttons, fire alarm systems or Building
Management Systems (BMS) by “free potential – normally closed” inputs. The installation of the emergency push button (MCP –
manual control point) is compulsory because, in addition to allowing manual emergency control, it also provides display of fault /
emergency warnings, and can be used for easy, remote resetting.
In order to provide comfort and energy saving, the natural ventilation is granted by operating automatically the windows, according
to the environmental conditions detected by the sensors. Windows can be manually controlled through push buttons or key switches
in 2 different ventilation zones.
C-SV and C-SV IB control panels have been designed and tested according to the European Standard EN 12101-10 and prEN 12101-9.
They have been certified as Smoke and Heat Control Systems according to the European Standard EN 12101-10:2005 + AC:2007 by IFT
Rosenheim (not for C-SV 13A and C-SV IB 13A versions)
SMOKE VENTILATION CONTROL PANELS – ACCESSORIES
OPTICAL SMOKE DETECTOR – 36418Q
Smoke detection by infrared light diffusion for Tyndall effect. It is certified according to the UNI EN 54 – 7/9 regulations. Alarm signal through the red led.
RESPONSE TIME 3 sec approx.
VOLTAGE SUPPLY 24 V (min. 10 V, max. 30 V)
TEMPERATURE RANGE -10° + 80° C
DEGREE OF HUMIDITY < 95%
MAX AIR SPEED 10 m/s
DETECTED SURFACE 40 m2
A frequent cleaning, especially in dusty environments, is recommended.
EMERGENCY PUSH BUTTON – 42140N
It’s necessary to break the safety glass to operate the emergency button. Emergency push button allow to control by LEDs the status of the system, reset the control panels and close the window at the end of the emergency
FLUSH MOUNT DOUBLE PUSH BUTTON – 41019H
Once connected to control panel allows to operate all window for natural ventilation.
NV KEY SWITCH – 41789B
Once connected to control panel allows to operate all window for natural ventilation.
If properly connected to C-SV, it can be used to send an emergency closing command.
WS WIND SENSOR – 37185V
It emits a variable signal according to
the wind intensity and acts on the
control panel as the rain sensors do.
TH THERMOSTAT – 40675K
The thermostat opens or closes
windows when temperature settings
are exceeded. Built in on/off switch.
ACOUSTIC ALARM DEVICE – 40892C
Outward self-fed siren 24 V, stainless
steel box with polycarbonate cover,
sound power 115 dB,
voltage supply 24V – 2 A,
battery 12 V, 2 Ah.
Dimensions: 236x280x99 mm
RS RAIN SENSOR – 40450K
In case of rain, the rain sensor sends
the signal for window automatic closing.
CO2 – 41773L
The CO2 sensor, if present, has the
priority on the manual control. Suitable
for conference and meeting rooms,
offices, schools/nurseries, passive and
low-energy buildings.
2 switch outputs CO2 controlled for
2 stage control, with manual and
automatic mode as well as display of
switching status.
3x 0–10 V outputs for CO2,
temperature and relative humidity.
Compatible C-SV, IB-SV only
DIAGNOSTIC KIT (CABLE + SOFTWARE) – 41853M
In the event of anomalies or installation
problems, it is possible to interrogate
the C-SV control panels using a special
diagnostic USB cable connected to a
simple computer. A dedicated software
allows you to monitor in real time the
operating parameters of the control
panel (primary power supply, battery
voltage, etc.) and to trace the origin of
any faults by reading the associated
error code.
BATTERIES FOR C-SV AND C-SV IB
40911V
Spare part for C-SV and C-SV IB control panel 4A or 8A, formed by two pieces of 12 V, 4,5 Ah batteries.
41921C
Spare part for C-SV and C-SV IB control panel 13A or 20A, formed by two pieces of 12 V, 9 Ah batteries.